Effective 8/13/99
Page 14
I.L. 70C1037H02
Figure 2.8 Zero Sequence Sensing Scheme for 3200A Frame
Breaker M2 trips since this is the only breaker seeing the I fault via element R .
No jumper on B-6, B-7 terminals - all breakers are programmed for standard Residual Ground Fault
protection.
AUX CTs not shown. Wiring needed at system level is shown as a dotted line.
Capital letters represent primary current. Lowercase letters represent secondary current.
The three breakers (M1, M2, and T) must all have the same breaker/sensor rating.
G5
Notes:
Figure 2.9 Multiple Source/Multiple Ground Scheme
R
5
R
5
R
5
f
f
T
M2
M1
B5
B4
I/2
G
I/2
G
I/2
G
I/2
G
I
G
I
G
i
g
i
g
i/2
g
i/2
G
i/2
g
i/2
g
i/2
g
Neutral Sensors Wired
in a Loop Configuration
B5
B5
B4
B4
N
N
Internal
Digitrip
Sensor
Ground Fault
Courtesy of NationalSwitchgear.com