IL17569
Page 7-4
Effective June, 2001
It is wise to verify the ability of the FP-5000 to open the breaker
and trip the load. The easiest way is by remote trip, via remote trip
contact or data communications. Many other internal functions can
be manipulated to force a relay trip.
Verify if the 52a and/or 52b contacts are used and the Breaker
Closed LED lights.
Verify that the trip coil monitor function is reading trickle current
around trip 1 relay.
Verify the phasor angles have correct polarity between voltage and
current inputs.