IL17569
Page 9-6
Effective June, 2001
Table 9.5 Logic Input Group Definitions
Group Individual Elements
Ph OC 50P-1, 50P-2, 51P
Gnd OC 50X-1, 50X-2, 50R-1, 50R-2, 51X,
51R
IOC 50X-1, 50X-2, 50R-1, 50R-2, 50P-1,
50P-2
TOC 51X, 51R, 51P
OC 50X-1, 50X-2, 50R-1, 50R-2, 50P-1,
50P-2, 51X, 51R, 51P
All Alarm 50X-3, 50R-3, 50P-3, 59-A2, 27-A2,
59-M2, 27-M2, 46-2, 47-2, 81U-2,
81O-2
Voltage 59-A1, 27-A1, 59-M1, 27-M1
Frequency 81U-1, 81O-1
All Protection 50X-1, 50X-2, 50R-1, 50R-2, 50P-1,
50P-2, 51X, 51R, 51P, 59-A1, 27-A1,
59-M1, 27-M1, 46-1, 47-1, 81U-1,
BF Pickup, Zone Gnd, Zone Phase
9.6.1 Example of Use
A simple example of the logic will illustrate the principles of
programming a logic diagram. This example shows how to add
a “High Load Alarm” function to the FP-5000.
Set the 50P-3 Phase IOC Alarm Pickup to 85% of the 51P TOC
Pickup setting. Go to “Set Mode” Protection ! Protection Setting
Group1 ! Alarms ! 50P-3 PH IOC Alarm ! Pickup and enter a
value of 0.85.
Use programmable logic to turn on the Auxiliary LED and energize
Output Relay 4.
Require the 50P-3 function pickup to be present for 1 second to
prevent spurious operation.
Maintain the output signal for 5 seconds after the current drops
below the pickup level.
Add an external switch to Contact Input 8 to enable or disable the
High Load Alarm at the user’s discretion.
A Timer Gate has an On Delay and/or an Off Delay that can be set
for up to 9999 cycles (166 minutes at 60 Hz). Use 60 cycles for an
On Delay of 1 second and 300 cycles for an Off Delay of 5 seconds.
Figure 9-5 is an implementation of the “High Load Alarm.”
The logic functions are programmed as follows from the main
settings menu:
Programmable Logic !
Logic Gate1 ! Function: AND
IN1: Input CIn8
IN2: Pickup 50P-3
Programmable Logic !
Timer Gate1 ! In: Logic LG1
On Delay (c): 60
Off Delay (c): 300
Output Config !
Output Rly4 ! Function: OR
IN1: Logic TGI
Output Config !
Output Aux LED ! Function: OR
IN1: Logic TGI