IL17569
Page 4-18
Effective June, 2001
Output Relay CFG
Output Trip1
Output Trip2
Output Rly3
Output Rly4
Output Rly5
Output Alarm
Output Aux LED
Trip Indicator
Alarm Indicator
Pickup Indicator
“Output Relay CFG” Display:
Output Rly4
Function: Disable
Dropout: Unlatched
Off Delay (c): 0
IN1: Trip Unused
IN2: Trip Unused
IN3: Unused
IN4: Breaker All Alm
“Output Rly4” Display:
Output Trip2
Monitor: Off
Function: Disable
Dropout Unlatched
Off Delay (c): 5
IN1: Unused
IN2: Unused
IN3: Unused
IN4: Unused
“Output Trip2Display:
Output Trip1
Monitor: On
Function: OR
Dropout: Off Delay
Off Delay (c): 5
IN1: AllProt
IN2: BreakerOpenBkr
IN3: Unused
IN4: Unused
“Output Trip1” Display:
Output Rly3
Function: OR
Dropout: Latched
Off Delay (c): 0
IN1: Trip BF
IN2: Unused
IN3: Unused
IN4: Unused
“Output Rly3” Display:
Output relay CFG
Output Rly5
Function: OR
Dropout: Off Delay
Off Delay (c): 1
IN1: Breaker Close BK
IN2: Unused
IN3: Unused
IN4: Unused
“Output Rly5” Display:
Output Gate Alarm
Function: OR
Dropout: Unlatched
Off Delay (c): 0
IN1: Trip AllProt
IN2: Trip All Alm
IN3: Sys Alm All Alm
IN4: Breaker All Alm
“Output Alarm” Display:
Output Aux LED
Function: OR
IN1: Unused
IN2: Unused
IN3: Unused
IN4: Unused
“Output Aux LED” Display:
Trip Indicator
Dropout: Latched
Trip1: Enable
Trip2: Enable
Rly3: Disable
Rly4: Disable
Rly5: Disable
Alarm: Disable
RIy Healthy: Disable
“Trip Indicator” Display:
Alarm Indicator
Dropout: Latched
Trip1: Disable
Trip2: Disable
Rly3: Disable
Rly4: Disable
Rly5: Disable
Alarm: Enable
Rly Healthy: Enable
“Alarm Indicator” Display:
Pickup Indicator
Dropout: Unlatched
IOC: Enable
TOC: Enable
Volt: Enable
OverFreq: Enable
UnderFreq: Enable
Unbalance: Enable
Prot Alarm: Disable
“Pickup Indicator” Display:

Table of Contents