IL17569
Page 5-10
Effective June, 2001
Table 5.2 Power Factor (continued)
Display Setting Description Setpoint Range/ Default Selected Refer to
Value Selection Setting Value Sec. #
55D Displacement Power Factor Settings 5.5.2.8
Displacement PF
Trigger PF: Select power factor to trigger on 0.50 to 1.00 (lag), -0.50 to Disable 5.5.2.8
-0.99 (lead), disable
(0.01 pu increments)
Reset PF: Select power factor to reset on 0.50 to 1.00 (lag), -0.50 to Disable 5.5.2.8
-0.99 (lead), disable
(0.01 pu increments)
Delay (s): Select delay time in seconds 0 to 1000 seconds 0 5.5.2.8
(1 second increments)
Table 5.2 Zone Interlocking: Selects Zone In and Zone Out settings
Zone Interlocking Zone Interlocking Settings 5.5.2.9
Zone in: Select zone in function Disable, Phase, Ground, Both Disable
8.5
Zone Out: Select zone out function Disable, Phase, Ground, Both Disable
Table 5.2 Alarms: Selects Alarms settings for all protection functions – 50P-3, 50X-3, 50R-3, 46-2, 47-2, 59-M2, 27M-2,
59A-2, 27A-2, 81O-2, and 81U-2
50P-3 PH IOC Phase Overcurrent Alarm Setting 5.5.2.10
Alarm 5.5.2.1
Pickup: Select current pickup value 0.1 to 20.0 pu, Disable Disable
8.3
in per unit values (x I
nom
) (0.01 increments)
Delay (c): Select delay time in cycles 0 to 9999 cycles 0
(1 cycle increments)
Direction: Directional control reserved (Fixed at Both) Both
for future use
50X-3 IX IOC Fourth Ct Overcurrent 5.5.2.10
Alarm Alarm Setting Alarm Setting 5.5.2.2
Pickup: Select current pickup value 0.1 to 20.0 pu, Disable Disable
8.3
in per unit values (x I
nom
) (0.01 increments)
Delay (c): Select delay time in cycles 0 to 9999 cycles 0
(1 cycle increments)
Direction: Directional control reserved (Fixed at Both) Both
for future use
50R-3 IR IOC Residual Time Overcurrent 5.5.2.3
Alarm Alarm Setting 5.5.2.10
Pickup: Select current pickup value 0.1 to 20.0 pu, Disable Disable
8.3
in per unit values (x I
nom
) (0.01 increments)
Delay (c): Select delay time in cycles 0 to 9999 cycles 0
(1 cycle increments)
Direction: Directional control reserved (Fixed at Both) Both
for future use