Page 5-11
IL17569
Effective June, 2001
Table 5.2 Alarms (continued)
Display Setting Description Setpoint range/ Default Selected Refer to
Value Selection Setting Value Sec. #
46-2 I Unbal Current Unbalance Alarm Settings 5.5.2.10
Alarm 5.5.2.4
Threshold: Select magnitude of 0.1 to 20.0 pu, Disable 0.1
8.3.5
unbalance required (0.01 increments)
(either I1 or I2)
% (I2/I1): Percent negative sequence (I2) 4 to 40 percent 40
divided by positive sequencel (I1) (1% increments)
Delay (c): Select delay time in cycles 0 to 9999 cycles 60
(1 cycle increments)
47-2 V Unbal Voltage Unbalance Alarm Settings 5.5.2.10
Alarm 5.5.2.4
Threshold: Select magnitude 1 to 100 volts, Disable 50
8.6.1
of unbalance required (1 volt increments)
(either V1 or V2)
% (V2/V1): Percent negative sequence (V2) 4 to 40 percent 40
divided by positive sequence (V1) (1% increments)
Delay (c): Select delay time in cycles 0 to 9999 cycles 60
(1 cycle increments)
59M-2 OV Alarm Main VT Overvoltage Alarm Setting 5.5.2.10
Threshold V: Select magnitude 10 to 150 volts, disable Disable
5.5.2.5
of overvoltage required (1 volt increments)
8.6.2
Delay (c): Select delay time in cycles 0 to 9999 cycles 0
(1 cycle increments)
27M-2 UV Alarm Main VT Undervoltage 5.5.2.10
Alarm Setting 5.5.2.5
Threshold V: Select magnitude 10 to 150 volts, disable Disable
8.6.2
of undervoltage required (1 volt increments)
Delay (c): Select delay time in cycles 0 to 9999 cycles 0
(1 cycle increments)
59A-2 OV Alarm Auxiliary VT Overvoltage 5.5.2.10
Alarm Setting 5.5.2.5
Threshold V: Select magnitude 10 to 250 volts, disable Disable
8.6.2
of overvoltage required (1 volt increments)
Delay (c): Select delay time in cycles 0 to 9999 cycles 0
(1 cycle increments)
27A-2 UV Alarm Auxiliary VT Undervoltage 5.5.2.10
Alarm Setting 5.5.2.5
Threshold V: Select magnitude 10 to 250 volts, disable Disable
8.6.2
of undervoltage required (1 volt increments)
Delay (c): Select delay time in cycles 0 to 9999 cycles 0
(1 cycle increments)