IL17569
Page 5-12
Effective June, 2001
Table 5.2 Alarms (continued)
Display Setting Description Setpoint Range/ Default Selected Refer to
Value Selection Setting Value Sec. #
81O-2 OF Alarm Overfrequency Alarm Settings 5.5.2.10
Threshold: Select threshold based 45 to 65 Hz, disable Disable
5.5.2.6
on power system frequency (0.01 increments)
8.8
Delay (c): Select delay time in cycles 0 to 9999 cycles 0
(1 cycle increments)
81U-2 UF Alarm Underfrequency Alarm Settings 5.5.2.10
Threshold: Select threshold based 45 to 65 Hz, disable Disable
5.5.2.6
on power system frequency (0.01 increments)
8.8
Delay (c): Select delay time in cycles 0 to 9999 cycles 0
(1 cycle increments)