Page 5-13
IL17569
Effective June, 2001
Table 5.3 System Alarms Phase time overcurrent (51P) and instantaneous (50P-1 & 50P-2) device settings
Display Setting Description Setpoint Range/ Default Selected Refer to
Value Selection Setting Value Sec. #
Watt Power System Watt Power Alarm Setting 5.5.3
Alarm
Units: Select units for watt power kW or MW kW
Threshold: Select magnitude threshold 1 to 40,000, Disable Disable
in primary units (increments of 1)
Delay (m): Select delay time in minutes 0 to 60 minutes 0
(increments of 1)
VAR Power System VAR Power Alarm Setting 5.5.3
Alarm
Units: Select units for VAR power kVAR or MVAR kVAR
Threshold: Select magnitude threshold 1 to 40,000, Disable Disable
in primary units (increments of 1)
Delay (m): Select delay time in minutes 0 to 60 minutes 0
(increments of 1)
VA Power Alarm System VA Power Alarm Setting 5.5.3
Units: Select units for VA power kVA or MVA kVA
Threshold: Select magnitude threshold 1 to 40,000, Disable Disable
in primary units (increments of 1)
Delay (m): Select delay time in minutes 0 to 60 minutes 0
(increments of 1)
Watt Demand System Watt Demand 5.5.3
Alarm Alarm Setting
Units: Select units for watt demand kW or MW kW
Threshold: Select magnitude threshold 1 to 40,000, Disable Disable
in primary units (increments of 1)
Delay (m): Select delay time in minutes 0 to 60 minutes 0
(increments of 1)
VAR Demand System VAR Demand 5.5.3
Alarm Alarm Setting
Units: Select units for VAR demand kVAR or MVAR kVAR
Threshold: Select magnitude threshold 1 to 40,000, Disable Disable
in primary units (increments of 1)
Delay (m): Select delay time in minutes 0 to 60 minutes 0
(increments of 1)