IL17569
Page 5-24
Effective June, 2001
Table 5.7 Programmable Logic (continued)
Display Setting Description Setpoint Range/ Default Selected Refer to
Value Selection Setting Value Sec. #
Timer Gate 1 Timer gate 1 Programmable Settings 5.5.7
9.3
Set Group: Select protection setting group 1, 2, 3, 4 or All 1 9.6
for Timer gate to apply
In: Logic input * See Logic Input Options Unused
Table 5.10
On Delay (c): Select timer gate on delay 0 to 9999 cycles 0
(1 cycle increments)
Off Delay (c): Select timer gate off delay 0 to 9999 cycles 0
(1 cycle increments)
Timer Gate 2 Timer gate 2 Settings 5.5.7
9.3
Set Group: Select protection setting group 1, 2, 3, 4 or All 1 9.6
for Timer gate to apply
In: Logic input * See Logic Input Options Unused
Table 5.20
On Delay (c): Select timer gate on delay 0 to 9999 cycles 0
(1 cycle increments)
Off Delay (c): Select timer gate off delay 0 to 9999 cycles 0
(1 cycle increments)
Timer Gate 3 Timer gate 3 Settings 5.5.7
9.3
Set Group: Select protection setting group 1, 2, 3, 4 or All 1 9.6
for Timer gate to apply
In: Logic input * See Logic Input Options Unused
Table 5.10
On Delay (c): Select timer gate on delay 0 to 9999 cycles 0
(1 cycle increments)
Off Delay (c): Select timer gate off delay 0 to 9999 cycles 0
(1 cycle increments)
Timer Gate 4 Timer gate 4 Settings 5.5.7
9.3
Set Group: Select protection setting group 1, 2, 3, 4 or All 1 9.6
for Timer gate to apply
In: Logic input * See Logic Input Options Unused
Table 5.10
On Delay (c): Select timer gate on delay 0 to 9999 cycles 0
(1 cycle increments)
Off Delay (c): Select timer gate off delay 0 to 9999 cycles 0
(1 cycle increments)