Page 5-25
IL17569
Effective June, 2001
Table 5.7 Programmable Logic (continued)
Display Setting Description Setpoint Range/ Default Selected Refer to
Value Selection Setting Value Sec. #
Timer Gate 5 Timer gate 5 Settings 5.5.7
9.3
Set Group: Select protection setting group 1, 2, 3, 4 or All 1 9.6
for Timer gate to apply
In: Logic input * See Logic Input Options Unused
Table 5.10
On Delay (c): Select timer gate on delay 0 to 9999 cycles 0
(1 cycle increments)
Off Delay (c): Select timer gate off delay 0 to 9999 cycles 0
(1 cycle increments)
Timer Gate 6 Timer gate 6 Settings 5.5.7
9.3
Set Group: Select protection setting group 1, 2, 3, 4 or All 1 9.6
for Timer gate to apply
In: Logic input * See Logic Input Options Unused
Table 5.10
On Delay (c): Select timer gate on delay 0 to 9999 cycles 0
(1 cycle increments)
Off Delay (c): Select timer gate off delay 0 to 9999 cycles 0
(1 cycle increments)
Logic Latch 1 Logic Latch 1 Settings 5.5.7
9.3
Set Group: Select protection setting group 1, 2, 3, 4 or All 1 9.6
for logic latch to apply
SIn: Select logic input to set latch * See Logic Input Options Unused
Table 5.10
RIn: Select logic input to reset latch * See Logic Input Options Unused
Table 5.10
Logic Latch 2 Logic Latch 2 Settings 5.5.7
9.3
Set Group: Select protection setting group 1, 2, 3, 4 or All 1 9.6
for logic latch to apply
SIn: Select logic input to set latch * See Logic Input Options Unused
Table 5.10
RIn: Select logic input to reset latch * See Logic Input Options Unused
Table 5.10