Instructions for the FP-6000 Protective Relay
Table 5. Table of Specifications (continued).
IPONI COMMUNICATIONS: TB3 J1
Baud Rate 9600 Fixed
Max. Distance 10,000 ft.
Protocol INCOM Slave
Media Shielded Twisted Pair - CH IMPCABLE; BELDEN 9463, 3072F
Signal Lines J1-1, J1-2 Polarity Not Needed
Shield J1-3 Filter Referenced to Chassis
dc Input Impedance ~2 ohms
ac Input Impedance @ 100 kHz > 30k/100 ohms Unterminated/Terminated - Switch
ACCESSORY BUS: TB3 J2 - FUTURE INTERFACE
Baud Rate 9600 Fixed
Max. distance 10,000 Ft. (254 m)
Protocol INCOM
Media Shielded Twisted Pair - CH IMPCABLE: Belden 9463, 3072F
Signal lines J2-1, 2-2 Polarity Not Needed
Shield J2-3 Filter Referenced to Chassis
dc input impedance ~2 ohms
ac Input impedance @ 100 kHz > 100 ohms (Permanent Termination Resistor)
ZONE INTERLOCK: TB3 J3
Zone Out J3-1 Open Collector Output ~ 4.5 V to Common
Zone In J3-4, Approximately 300K ohms Input Impedance
Zone Common J3-2, 3-5 Internally Connected
Zone Shield J3-3 Referenced Direct to Chassis – NOT REQUIRED
Cable 14-18 AWG Twisted Pair <250' Between 1
st
and Last Unit
RS-232: FRONT TEMPORARY PROGRAMMING MONITOR PORT POWERPORT CONNECTION
Baud Rate 38.4 kB, 19.2 kB, 9.6 kB
Connector Standard 9-Pin D Subminiature, DCE Connection P2, 3, 5
Protocol INCOM ASCII Slave
Cable Shielded & Restricted to < 3 m (9.8 ft.) in Length
METERING ACCURACY:
Input Signal Frequency Necessary for Accurate Operation 60 Hz Nominal, 57-63 Hz (5%)
50 Hz Nominal, 47-53 Hz (5%)
Frequency Measurement Accuracy +
0.02 Hz
Clock Accuracy Free Running +
1 minute/month @ 25°C (77°F).
Automatically Updated by PowerNet Host when Present