Page 22 Effective: May 2008
Instructions for the FP-6000 Protective Relay
For more information visit: www.eaton.com IB02602004E
1 FS (Full Scale) = 3 • CT Rating • Nominal L-N Voltage.
2 Minimum absolute tolerance of measured current is 0.5% of CT rating.
3 Minimum absolute tolerance of residual current is 3% of CT rating.
4 Minimum absolute tolerance of measured voltage is 0.5% of nominal voltage.
5 Tolerance for currents greater than 1.03 times pickup (1.5 times pickup at minimum pickup setpoints).
6 Note shield & VG exception details in Section 7-Startup.
3.2 Standards Compliance
The FP-6000 complies with the following standards except where
noted:
ANSI/IEEE C37.90-1989, Standard for Relay Systems associated
with electric power apparatus.
UL/CUL-1053 Recognized – Ground Fault Sensing and Relaying
Equipment File E154862:
FP6200-00 5A CT model only
FP6300-00 1A CT pending
EMC Requirements:
ANSI C37.90.1 (1989) Surge withstand all ports
ANSI C37.90.2 (1995) RF withstand
Emissions (EN-50081-2):
EN 50011CISPR-11, Class A
CFR 47 FCC Part 15 Subpart b Class A
Immunity (EN-61000-6-2):
ENV 61000-4-2ESD Immunity
ENV 61000-4-3RF Radiated Immunity
ENV 61000-4-4EFT Immunity
EN 61000-4-5Surge Withstand
EN 61000-4-6RF Conducted Immunity
EN 61000-4-8Power Frequency Magnetic Field Immunity
EN 61000-4-11Voltage Dips, Short Interruption and Voltage
Variation Immunity
See Appendix Section 13.5 for compliance levels and related
information.
Table 5. Table of Specifications (continued).
COMMON MODE VOLTAGE WITHSTAND >1500 VRMS/1 MINUTE, ANY PORT TO CHASSIS6
ENVIRONMENTAL RATINGS:
Operating Temp -40°C to +60°C (-40°F to +140°F) Dry heat + 70°C (158°F).
Storage Temp -40°C to +85°C (-40°F to +185°F).
Humidity 5% to 95% Relative Humidity (Non-Condensing)
Altitude 0 to 2500 m (8,202 ft.) Above Mean Sea Level
DIMENSIONS
Behind Panel:
Height 6.7 in. (17.0 cm)
Width 5.3 in. (13.5 cm)
Depth 6.9 in. (17.75 cm)
In Front of Panel:
Height 11.34 in. (28.9 cm)
Width 7.72 in. (19.7 cm)
Depth 0.80 in. (2.1 cm)
Weight:
Drawout 5.8 lbs (2.6 Kg)
Enclosure 5.0 lbs (2.3 Kg)
Adapter Panel 1.3 lbs (.6 Kg)
Shipping 16.5 lbs (7.5 Kg)