6 Parameters
96 DC1 Frequency Inverter 10/12 MN04020003Z-EN www.eaton.com
Extended parameter range (access: P-14 = 101)
P-15 143 – rw Function of digital inputs 5
0 - 12 Defines the function of the digital inputs depending on the control
mode setting in P-12.
P-16
144 ✓ rw Analog input 1 (AI1), signal range V0-10
V0- 10 0 - 10 V signal (unipolar)
The frequency inverter will remain at 0.0 Hz if the analog signal is
< 0.0% after scaling and applying the corresponding offset.
b-10-10 0 - 10 V signal (bipolar).
The frequency inverter will drive the motor in the reverse operating
direction as soon as the analog reference value is less than 0.0 % after
scaling and applying the corresponding offset.
A0-20A 0 - 20 mA signal
t4-20 4 - 20 mA signal
The frequency inverter will be switched off and show failure code
4-20F as soon as the signal level falls below 3 mA.
r4-20 4 - 20 mA signal
The frequency inverter will run as per a ramp all the way to a stop as
soon as the signal level falls below 3 mA.
t20-4 20 - 4 mA Signal
The frequency inverter will be switched off and show failure code
4-20F as soon as the signal level falls below 3 mA.
r20-4 20 - 4 mA Signal
The frequency inverter will run as per a ramp all the way to a stop as
soon as the signal level falls below 3 mA.
P-17 145 ✓ rw 4 - 32 kHz Pulse frequency 16
1)
Size FS1: 16 kHz
Sizes FS2 and FS3: 8 kHz
Used to set the frequency inverter's maximum rms pulse frequency.
If rED is shown, the pulse frequency has been reduced to the level in
P00-14 due to an elevated heat sink temperature in the frequency
inverter.
P-18
146 ✓ rw K1 signal (Relay Output 1) 0
Used to select the function assigned to the relay output.
The relay has two output terminals: Logic 1 indicates that the relay is
active: This is why terminals 10 and 11 are connected to each other.
Output terminals; logic 1 indicates that the relay is active.
0 RUN, enable (FWD, REV)
1 READY, frequency inverter ready for operation
2 Output frequency = frequency reference value
3 Error message (frequency inverter not ready)
4 Output frequency ≧ limit value (P-19)
5 Output current ≧ limit value (P-19)
6 Output frequency < limit value (P-19)
7 Output current < limit value (P-19)