6 Parameters
102 DC1 Frequency Inverter 10/12 MN04020003Z-EN www.eaton.com
P-47 175 ✓ rw Analog input 2 signal format t 4-20
V0-10 0 - 10 V signal
A0-20 0-20mA
t4-20 4-20mA (≦ 3mA → error message: 4-20F)
r4-20 4 - 20 mA (≦ 3mA → delay time 1)
t20-4 20 - 4 mA (≦ 3mA → error message: 4-20F)
r20-4 20 - 4 mA (≦ 3mA → delay time 1)
P-48
176 ✓ rw 0.0 - 25.0 s Standby time
0 = Deactivated
The drive will switch to standby mode (i.e., output deactivated) if the
minimum speed (P-02) remains constant during the length of time spec-
ified here.
20
P-49
177 ✓ rw 0.0 - 100.0 % PI feedback wake up level
Error value (difference between PI setpoint and process value) for the
PI controller. If the value measured by the PI controller is higher than
this value, the drive will leave the stand-by mode.
0
P-50
178 ✓ rw CANopen baud rate for CANopen communications 2
0 125 kbit/s
1 250 kBit/s
2 500 kBit/s
3 1000 kBit/s
P00-…-Display values
P00-01 20 ro % Analog input 1
100 % = Maximum input voltage
P00-02 21 ro % Analog input 2
100 % = Maximum input voltage
P00-03 23 ro Hz/rpm Frequency reference value / Motor shaft speed
Shown in Hz if P-10 = 0; otherwise shown in rpm
P00-04
11 ro DI1 - DI4 status Digital inputs 1 - 4
State of the frequency inverter‘s digital input
P00-05 ro 0 reserved
P00-06 ro 0 reserved
P00-07 ro V Motor voltage: the value of the rms voltage being applied at the motor
P00-08 23 ro V Internal DC bus voltage
P00-09 24 ro °C Unit Temperature
Heatsink temperature in °C
P00-10
ro HH:MM:SS The frequency inverter’s operating time
Not affected when the parameters are reset to their default settings.
PNU
ID Access rights Value Description DS
RUN ro/rw