6 Parameters
6.2 Digital and analog inputs
108 DC1 Frequency Inverter 10/12 MN04020003Z-EN www.eaton.com
6.2.1 Digital Input (DI)
Control signal terminals 2, 3, 4, and 6 can be used as digital inputs (DI). The
digital inputs‘ function and mode of operation are configured in parameter
P-15.
Example
Desired options:
• Clockwise rotating field (FWD),
• Anticlockwise rotating field (REV),
• external fault,
• Setpoint value via AI1.
Figure 59: Example of an external fault (EXT)
Table 14: Digital input wiring
• DI1 (control signal terminal 2): FWD (Forward = Start enable clockwise
rotating field)
• DI2 (control signal terminal 3): REV (Reverse = Start enable anti-clock-
wise rotating field)
• DI3 (control signal terminal 4): external fault
• AI1 (control signal terminal 6): analog setpoint value
P-15 DI1 DI2 DI3 AI1
7 0 = locked
1 = Start enable FWD
0 = locked
1 = Start enable REV
External fault
0 = Fault
1 = Enable
Setpoint value AI1
(0 - 10 V)
DI1 + DI2 = Quick stop (P-24)
2
DI1
FWD
+24 V
3
DI2
REV
4
DI3
EXT
6
AI1
f-Soll
1
+24 V Out
< 100 mA
0...+10 V/
20 mA
P-12 = 0
P-15 = 7