6 Parameters
6.2 Digital and analog inputs
110 DC1 Frequency Inverter 10/12 MN04020003Z-EN www.eaton.com
6.2.2.1 Scaled value range (AI1)
The following graphs show examples of the curve characteristics of the
scaled and non-scaled input signals.
Example: P-35 = 200 %
If parameter P-16 is configured for a 0 - 10 V signal and parameter P-35 is set
to 200 %, a 5 V input will result in the frequency inverter running at its maxi-
mum frequency/speed (P-01). Values lower than 100 % limit the maximum
frequency; values greater than 100 % are used for low signal levels, e.g. for
sensors with a 0 to 5 V output.
Figure 61: Scaled input signal
100 % f
AI1
P-35 = 200 %
(10 V)
5 V ≙ 100 %
P-01