6 Parameters
6.2 Digital and analog inputs
122 DC1 Frequency Inverter 10/12 MN04020003Z-EN www.eaton.com
P-31 159 ✓ rw REAF, Start function with automatic restart, operating unit 1
This parameter will only be active if the keypad control operating mode
is being used (P-12 = 1 or P-12 = 2).
0 Minimum speed; keypad
The keypad’s start and stop pushbuttons are enabled, and control
signal terminals 1 and 2 must be connected.
The frequency inverter will always start with the minimum frequency/
speed (P-02).
1 Previous speed, keypad
The keypad’s start and stop pushbuttons are enabled; control signal
terminals 1 and 2 must be connected.
The frequency inverter will always start with the most recent operating
frequency/speed.
2 Minimum speed; terminal
The frequency inverter will be started directly from the control signal
terminals; the keypad's start and stop buttons will be ignored.
The frequency inverter will always start with the minimum frequency/
speed (P-02).
3 Previous speed, terminal
PNU ID Access rights Value Description DS
RUN ro/rw