6 Parameters
6.2 Digital and analog inputs
134 DC1 Frequency Inverter 10/12 MN04020003Z-EN www.eaton.com
P-18 146 ✓ rw K1 signal (Relay Output 1) 0
Used to select the function assigned to the relay output.
The relay has two output terminals: Logic 1 indicates that the relay is
active: This is why terminals 10 and 11 are connected to each other.
Output terminals; logic 1 indicates that the relay is active.
0 RUN, enable (FWD, REV)
1 READY, frequency inverter ready for operation
2 Output frequency = frequency reference value
3 Error message (frequency inverter not ready)
4 Output frequency ≧ limit value (P-19)
5 Output current ≧ limit value (P-19)
6 Output frequency < limit value (P-19)
7 Output current < limit value (P-19)
P-19 147 ✓ rw K1-Limit value (relay) 100.0
P-02 - 200.0 %
The adjustable limit value that is being used in connection with
settings 4 to 7 of P-18 and P-25
P-25
153 ✓ rw Switch to digital output 8
DA4 (Digital output) → +24 V DC (Value 0 - 7)
0 RUN (Frequency inverter released and running / FWD, REV)
1 READY, frequency inverter ready for operation / no faults
2 Output frequency = frequency reference value
3 Error message (frequency inverter is not ready)
4 Output frequency ≧ limit value (P-19)
5 Output current ≧ limit value (P-19)
6 Output frequency < limit value (P-19)
7 Output current < limit value (P-19)
AO1 signal (Analog Output)
Analog output → 0 - 10 V DC (value 8 / 9)
8 Output frequency f-Out → 0 - 100 % f
max
(P-01)
9 Output current → 0 - 200 % I
e
(P-08)
P-32 160 ✓ rw 0 - 25 s DC-braking 0
Used to define the length of time during which direct current will be
applied to the motor if the output frequency reaches a value of 0.0 Hz.
Note:
The voltage level will be the same as the voltage amplification set in
P-11.
PNU
ID Access rights Value Description DS
RUN ro/rw