18 INSTALLATION AND OPERATION MANUAL 25-16328-B November 2020 www.eaton.com
Section 1: System installation and design
Alarm counter (Option 7.13 of EN54 pt 2)
The Panel has provision to record the number of instances that the CIE enters the
fire alarm condition.
The information is available at access level 2.
TEST (Option 16 of EN54)
The Panels equipped with the test option and can be implemented by either
Zone or Address.
Alarm verification
The Panel has the facility for global alarm verification where the detector alarm
decision is integrated over 30seconds.
Cable & wiring
Only the cable types listed below are allowable for loopconnections.
1. Enhanced Fire TUF™
2. Fire TUF™
3. FP200
4. MICC
When choosing your preferred cable type, you must take note of the following cable
and wiring requirements.
1. The cable must be 2 core screened with an over sheath.
2. Maximum loop length with any of the above cables is2KM.
3. Maximum volt drop must be limited to 7 volts.
4. The conductors should be 1.5mm minimum.
5. Multicore cable should not be used for detector wiring.
6. Different loops should NEVER be run within the samecable.
7. Loop feeds and returns should never be used within the same cable.
Cable resistance
Core diameter Typical FP200 resistance
1.0mm² 18.1 Ohms/km/Core
1.5mm² 12.1 Ohms/km/Core
2.5mm² 7.41 Ohms/km/Core
4.0mm² 4.61 Ohms/km/Core