31INSTALLATION AND OPERATION MANUAL 25-16328-B November 2020 www.eaton.com
Section 2: Commissioning
Panel outputs
Coincidence detection
Each panel output can be assigned a unique list of zones derived from the zones
available on the loop, to activate this output, two unique zones from this list have
to be be in fire or alternatively any zone outside this list will trigger the output also.
When the ‘coincidence’ box is checked- the ‘Allocate device’ button allows the user
to populate this list.