45INSTALLATION AND OPERATION MANUAL 25-16328-B November 2020 www.eaton.com
Section 3: Panel controls & indicators
Installation instructions for: Single channel input unit MCIM-C
Installation
1. Fit the box in position using the mounting detailsbelow.
2. Connect the unit according to the diagram below.
3. Recommended Loop Cable Type: FIRETUF, FP200,MICC.
ote: N No addressing of the interface is required. See control panel operation
for details.
This needs to be programmed as a call point on site installed PC software.
Standard connections
ote: N
1. Only connect cable screen to its adjacent earthterminal.
2. The end of line resistor provided must always be fitted, even if the
input is unused.
3. Monitored inputs can detect open or short circuitfaults.
Loop In +
Loop In -
Loop Out +
Loop Out -
Earth
Earth
IN +
IN -
EARTH
INTPUT
MCIM-C
LOOP
35 mm
18.5 mm
63 mm
s
Mounting Details (Drilling positions, template over leaf)
37.5mm
20 mm
22k
Loop In