Instruction Leaflet DT3000
Page 56 Effective: Date 07/02 I.B. 17555D
For more information visit: www.cutler-hammer.eaton.com
Supersedes I.B. 17555C dated November 1999
Figure 7-15 ANSI Extremely Inverse Curves (SC-6687-96)
0.01
0.10
1.00
10.00
100.00
1000.00
1 10 100
Multiple of Pickup Current (I/I
pu
)
Trip Time (seconds)
3
5
2
1
0.5
0.3
0.2
0.1
Time
Multiplier
Adjustable Time Mult iplier (0.1………5.0)
Tolerance: Time Multiplier Tolerance is ± 10% or ± 0.09 s,
w hichever is larger (> 1.5 x I
pu
)
For Ground Pickup <
0.2
pu
: trip time tolerance is ± 15%
Minimum Trip Time is 2 pow er line cycles