8 SmartWire-DT
8.9 Programming
182 DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
Example
Basic requirements:
DS7 soft starter: rated motor current = 55 A
Motor: rated motor current = 41 A
Current measurement with measuring range of 0 - 400 A
Calculation:
Writing to PNU 290.0 with I = 41 A
Measured current: 82 A
Scaling on PNU 290.0 = 41 A
I
rel
= 82 A / 41 A 200 % 0x4000
Value transmitted to DS7 soft starter: 0x4000

Table of Contents