EDR-5000 IM02602007E
Parameter Description Setting range Default Menu path
Scale Factor 18 The scale factor is used to convert the measured value in
an integer format
0.001,
0.01,
0.1,
1,
10,
100,
1000,
10000,
100000,
1000000
1 [Device Para
/DNP
/Point map
/Analog Input]
Dead Band 18 If a change of measured value is greater than the
deadband value it will be reported to the master.
0.01 - 100.00% 1% [Device Para
/DNP
/Point map
/Analog Input]
Analog value 19 Analog value can be used to report values to the master
(DNP)
1..n, TrendRecList -.- [Device Para
/DNP
/Point map
/Analog Input]
Scale Factor 19 The scale factor is used to convert the measured value in
an integer format
0.001,
0.01,
0.1,
1,
10,
100,
1000,
10000,
100000,
1000000
1 [Device Para
/DNP
/Point map
/Analog Input]
Dead Band 19 If a change of measured value is greater than the
deadband value it will be reported to the master.
0.01 - 100.00% 1% [Device Para
/DNP
/Point map
/Analog Input]
Analog value 20 Analog value can be used to report values to the master
(DNP)
1..n, TrendRecList -.- [Device Para
/DNP
/Point map
/Analog Input]
www.eaton.com 333