Parameter Description Setting range Default Menu path
Scale Factor 26 The scale factor is used to convert the measured value in
an integer format
0.001,
0.01,
0.1,
1,
10,
100,
1000,
10000,
100000,
1000000
1 [Device Para
/DNP
/Point map
/Analog Input]
Dead Band 26 If a change of measured value is greater than the
deadband value it will be reported to the master.
0.01 - 100.00% 1% [Device Para
/DNP
/Point map
/Analog Input]
Analog value 27 Analog value can be used to report values to the master
(DNP)
1..n, TrendRecList -.- [Device Para
/DNP
/Point map
/Analog Input]
Scale Factor 27 The scale factor is used to convert the measured value in
an integer format
0.001,
0.01,
0.1,
1,
10,
100,
1000,
10000,
100000,
1000000
1 [Device Para
/DNP
/Point map
/Analog Input]
Dead Band 27 If a change of measured value is greater than the
deadband value it will be reported to the master.
0.01 - 100.00% 1% [Device Para
/DNP
/Point map
/Analog Input]
Analog value 28 Analog value can be used to report values to the master
(DNP)
1..n, TrendRecList -.- [Device Para
/DNP
/Point map
/Analog Input]