Parameter Description Setting range Default Menu path
Scale Factor 28 The scale factor is used to convert the measured value in
an integer format
0.001,
0.01,
0.1,
1,
10,
100,
1000,
10000,
100000,
1000000
1 [Device Para
/DNP
/Point map
/Analog Input]
Dead Band 28 If a change of measured value is greater than the
deadband value it will be reported to the master.
0.01 - 100.00% 1% [Device Para
/DNP
/Point map
/Analog Input]
Analog value 29 Analog value can be used to report values to the master
(DNP)
1..n, TrendRecList -.- [Device Para
/DNP
/Point map
/Analog Input]
Scale Factor 29 The scale factor is used to convert the measured value in
an integer format
0.001,
0.01,
0.1,
1,
10,
100,
1000,
10000,
100000,
1000000
1 [Device Para
/DNP
/Point map
/Analog Input]
Dead Band 29 If a change of measured value is greater than the
deadband value it will be reported to the master.
0.01 - 100.00% 1% [Device Para
/DNP
/Point map
/Analog Input]
Analog value 30 Analog value can be used to report values to the master
(DNP)
1..n, TrendRecList -.- [Device Para
/DNP
/Point map
/Analog Input]