Troubleshooting (For further information, visit the www.eaton.com site or contact after-sales support.)
◗ The battery backup outlets 9
are not supplied with power.
◗ The connected devices are not
supplied when AC power fails.
◗ AC power is available, but the
UPS operates on battery power.
◗ The ltered outlets 8 are not
supplied.
◗ Green button 13 ashes
frequently and audio alarm
beeps.
◗ Red LED 12 is on and the
audio alarm beeps every 30
seconds.
◗ Red LED 11 is on and the
audio alarm beeps every 30
seconds.
◗ Green LED 10 is off and the
ltered outlets 8 are supplied.
◗ The telephone line is disturbed
or modem access is not
possible.
◗ Red LED 11 ashes.
Problem Diagnostic Solution
◗ Button 13 is not lighted on.
◗ The devices are not connected to
the battery backup outlets 9 .
◗ Circuit breaker 14 , located under
the UPS, has been tripped by an
overload on the UPS output.
◗ The wall outlet is not supplied.
◗ Circuit breaker 14 , located under
the UPS, has been tripped by an
overload on the UPS output.
◗ The UPS frequently operates on
battery power because the AC
power source is of poor quality.
◗ The UPS battery backup outlets 9
are overloaded.
◗ A fault has occurred on the UPS.
The battery backup outlets 9 are
no longer supplied.
◗ Surge protection is no longer
provided.
◗ Surge protection on the telephone
line is no longer provided.
◗ The battery has reached the end
of its service life.
◗ Press button 13 and check that it
turns green.
◗ Connect the devices to the battery
backup outlets 9 .
◗ Disconnect excess equipment
and reset the circuit breaker 14 by
pressing the corresponding button.
◗ Supply power to the wall outlet.
◗ Disconnect excess equipment
and reset the circuit breaker 14 by
pressing the corresponding button.
◗ Have the electrical installation
checked by a professional or use
another wall outlet.
◗ Disconnect excess equipment
connected to the battery backup
outlets 9 .
◗ Call after-sales support.
◗ Call after-sales support.
◗ Disconnect the telephone line from
the wall outlet.
◗ Call after-sales support.
◗ Have the battery replaced.
1
2
3
4
5
6
7
8
9
10
Advanced customizing of your UPS:
Sensitivity to variations of the AC power supply
◗ Only to be used if frequent switching to the UPS
battery due to large variations in the AC supply
voltage.
◗ Accessing the programming mode: with the device
switched off, press button 13 for 6 s and release it
once LEDs 11 12 13 have come on.
◗ Display of the 3 possible voltage ranges according to
the status of LEDs 11 and 12 :
Audio alarm
◗ Possibility of deactivating the audio alarm when the
UPS is operating on the battery.
◗ Accessing the programming mode: with the device
switched off, press button 13 for 11 s and release it
when the audio alarm sounds.
◗ Display of the 2 possible audio alarm modes:
Normal mode
(factory
conguration):
AC supply
between 184V
and 264V
Low range
mode:
AC supply
between 161V
and 264V
Low and high
range mode:
AC supply
between 161V
and 284V
◗ Memorizing the mode: 10 s after the last press of the
button.
◗ Memorizing the mode: 5 s after the last press of the
button.
Normal mode (factory
conguration):
the UPS emits a beep
every 10 s when operating
on its battery.
Silent mode:
the UPS emits a single
beep when switching to
battery operation and
then remains silent.
Normal mode
activated:
programming
by continuous
beep.
Silent mode
activated:
programming
by a beep every
second.
Change from one mode to another by successively
pressing button 13 while the sound is audible.