EMR-4000 IM02602009E
Parameter Description Setting range Default Menu path
t-Blo-UnderLoad Underload Start Delay. 37[x] elements are blocked for the
time programmed under this parameter, while the motor
is starting
0 - 1200s 60s [Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
t-Blo-IUnbalance Current Unbalance Start Delay. 46[x] elements are
blocked for the time programmed under this parameter,
while the motor is starting
0.03 - 1200.00s 10.00s [Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
t-Blo-JAM Jam Start Delay. 50J[x] elements are blocked for the time
programmed under this parameter, while the motor is
starting
0.03 - 1200.00s 60.00s [Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
t-Blo-VUnbalance Voltage Unbalance Start Delay. These elements are
blocked for the time programmed under this parameter,
while the motor is starting.
0 - 1200s 1s [Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
t-Blo-Undervoltage Undervoltage Start Delay. These elements are blocked
for the time programmed under this parameter, while the
motor is starting
0 - 1200s 1s [Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
t-Blo-Overvoltage Overvoltage Start Delay. These elements are blocked for
the time programmed under this parameter, while the
motor is starting
0 - 1200s 1s [Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
t-Blo-Power Power Start Delay. These elements are blocked for the
time programmed under this parameter, while the motor
is starting
0.03 - 1200.00s 0.03s [Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
t-Blo-PowerFactor Power Factor Start Delay. These elements are blocked
for the time programmed under this parameter, while the
motor is starting
0.03 - 1200.00s 0.03s [Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
t-Blo-Frequency Frequency Start Delay. These elements are blocked for
the time programmed under this parameter, while the
motor is starting
0 - 1200s 1s [Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
www.eaton.com 448