EMR-4000 IM02602009E
Setting Group Parameters of the Underload Module
Parameter Description Setting range Default Menu path
Function Permanent activation or deactivation of module/element. Inactive,
Active
Inactive [Protection Para
/<1..4>
/Underload-Prot
/37[1]]
ExBlo Fc Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive [Protection Para
/<1..4>
/Underload-Prot
/37[1]]
Blo TripCmd Permanent blocking of the Trip Command of the
module/element.
Inactive,
Active
37[1]: Inactive
37[2]: Active
37[3]: Inactive
[Protection Para
/<1..4>
/Underload-Prot
/37[1]]
ExBlo TripCmd Fc Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
Inactive,
Active
Inactive [Protection Para
/<1..4>
/Underload-Prot
/37[1]]
Underload Underload Pickup based on a multiplier of FLA 0.05 - 0.90FLA 0.50FLA [Protection Para
/<1..4>
/Underload-Prot
/37[1]]
Phases Indicates if one, two of three or all phases are required
for operation
any one,
all
any one [Protection Para
/<1..4>
/Underload-Prot
/37[1]]
t Tripping delay 0.4 - 1200.0s 37[1]: 10.0s
37[2]: 10.0s
37[3]: 0.4s
[Protection Para
/<1..4>
/Underload-Prot
/37[1]]
www.eaton.com 483