EMR-4000 IM02602009E
Having tripped the relay in the previous test, now decrease the phase A voltage. The dropout of »
%(V2/V1)«
has to be
1% below the »
%(V2/V1)«
setting.
Successful test result:
The measured trip delays, threshold values, and dropout ratios are within the permitted deviations/tolerances, specified
under Technical Data.
www.eaton.com 625