Setting Group Parameters of the RTD Temperature Protection Module
Parameter Description Setting range Default Menu path
Function Permanent activation or deactivation of module/element. Inactive,
Active
Inactive [Protection Para
/<1..4>
/Temp-Prot
/RTD
/General Settings]
ExBlo Fc Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive [Protection Para
/<1..4>
/Temp-Prot
/RTD
/General Settings]
Blo TripCmd Permanent blocking of the Trip Command of the
module/element.
Inactive,
Active
Inactive [Protection Para
/<1..4>
/Temp-Prot
/RTD
/General Settings]
ExBlo TripCmd Fc Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
Inactive,
Active
Inactive [Protection Para
/<1..4>
/Temp-Prot
/RTD
/General Settings]
WD 1 Alarm
Function
Winding 1 Alarm Function Inactive,
Active
Active [Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 1]
WD 1 Trip Function Winding 1 Trip Function Inactive,
Active
Active [Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 1]
www.eaton.com 716