EMR-4000 IM02602009E
Parameter Description Setting range Default Menu path
LB 1 Trip Load Bearing 1 Threshold for Temperature Trip
Only available if: Device Planning: Trip Function = Use
0 - 200°C 80°C [Protection Para
/<1..4>
/Temp-Prot
/RTD
/LB 1]
LB 2 Alarm Function Load Bearing 2 Alarm Function Inactive,
Active
Active [Protection Para
/<1..4>
/Temp-Prot
/RTD
/LB 2]
LB 2 Trip Function Load Bearing 2 Trip Function Inactive,
Active
Active [Protection Para
/<1..4>
/Temp-Prot
/RTD
/LB 2]
LB 2 Alarm Load Bearing 2 Threshold for Temperature Alarm
Only available if: Device Planning: Alarm Function = Use
0 - 200°C 80°C [Protection Para
/<1..4>
/Temp-Prot
/RTD
/LB 2]
LB 2 t-Delay Load Bearing 2 If this time is expired a Temperature
Alarm will be generated.
Only available if: Device Planning: Alarm Function = Use
0 - 360min 1min [Protection Para
/<1..4>
/Temp-Prot
/RTD
/LB 2]
LB 2 Trip Load Bearing 2 Threshold for Temperature Trip
Only available if: Device Planning: Trip Function = Use
0 - 200°C 80°C [Protection Para
/<1..4>
/Temp-Prot
/RTD
/LB 2]
Aux1 Alarm
Function
Auxiliary 1 Alarm Function Inactive,
Active
Active [Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux1]
www.eaton.com 723