EMR-4000 IM02602009E
Parameter Description Setting range Default Menu path
Aux1 Trip Function Auxiliary 1 Trip Function Inactive,
Active
Active [Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux1]
Aux1 Alarm Auxiliary 1 Threshold for Temperature Alarm
Only available if: Device Planning: Alarm Function1 =
Use
0 - 200°C 80°C [Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux1]
Aux1 t-Delay Auxiliary 1 If this time is expired a Temperature Alarm will
be generated.
Only available if: Device Planning: Alarm Function1 =
Use
0 - 360min 1min [Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux1]
Aux1 Trip Auxiliary 1 Threshold for Temperature Trip
Only available if: Device Planning: Trip Function2 = Use
0 - 200°C 100°C [Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux1]
Aux2 Alarm
Function
Auxiliary 2 Alarm Function Inactive,
Active
Active [Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux2]
Aux2 Trip Function Auxiliary 2 Trip Function Inactive,
Active
Active [Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux2]
Aux2 Alarm Auxiliary 2 Threshold for Temperature Alarm
Only available if: Device Planning: Alarm Function2 =
Use
0 - 200°C 80°C [Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux2]
www.eaton.com 724