Parameter Description Setting range Default Menu path
Aux2 t-Delay Auxiliary 2 If this time is expired a Temperature Alarm will
be generated.
Only available if: Device Planning: Alarm Function2 =
Use
0 - 360min 1min [Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux2]
Aux2 Trip Auxiliary 2 Threshold for Temperature Trip
Only available if: Device Planning: Trip Function2 = Use
0 - 200°C 100°C [Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux2]
WD Alarm Function Winding Alarm Function Inactive,
Active
Inactive [Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD Group]
WD Trip Function Winding Trip Function Inactive,
Active
Inactive [Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD Group]
WD Alarm Winding Threshold for Temperature Alarm
Only available if: Device Planning: Alarm Function = Use
0 - 200°C 80°C [Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD Group]
WD t-Delay Winding If this time is expired a Temperature Alarm will
be generated.
Only available if: Device Planning: Alarm Function = Use
0 - 360min 1min [Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD Group]
WD Trip Winding Threshold for Temperature Trip
Only available if: Device Planning: Trip Function = Use
0 - 200°C 100°C [Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD Group]
www.eaton.com 725