EMR-4000 IM02602009E
Parameter Description Setting range Default Menu path
MB Alarm Function Motor Bearing Alarm Function Inactive,
Active
Inactive [Protection Para
/<1..4>
/Temp-Prot
/RTD
/MB Group]
MB Trip Function Motor Bearing Trip Function Inactive,
Active
Inactive [Protection Para
/<1..4>
/Temp-Prot
/RTD
/MB Group]
MB Alarm Motor Bearing Threshold for Temperature Alarm
Only available if: Device Planning: Alarm Function = Use
0 - 200°C 80°C [Protection Para
/<1..4>
/Temp-Prot
/RTD
/MB Group]
MB t-Delay Motor Bearing If this time is expired a Temperature Alarm
will be generated.
Only available if: Device Planning: Alarm Function = Use
0 - 360min 1min [Protection Para
/<1..4>
/Temp-Prot
/RTD
/MB Group]
MB Trip Motor Bearing Threshold for Temperature Trip
Only available if: Device Planning: Trip Function = Use
0 - 200°C 100°C [Protection Para
/<1..4>
/Temp-Prot
/RTD
/MB Group]
LB Alarm Function Load Bearing Alarm Function Inactive,
Active
Inactive [Protection Para
/<1..4>
/Temp-Prot
/RTD
/LB Group]
LB Trip Function Load Bearing Trip Function Inactive,
Active
Inactive [Protection Para
/<1..4>
/Temp-Prot
/RTD
/LB Group]
www.eaton.com 726