Serial Interface Operation
Eaton ePDU G3 Operation Manual P-164000277—Rev 1 www.eaton.com/ePDU 77
PDU.Input[1].Phase[x].ChangedStatus.OverVoltage Timestamp Timestamp of last changing state of the alarm that has the
same name in the collection PresentStatus.
s RO
PDU.Input[1].Phase[x].Current Measure Current Measurement. mA RO
PDU.Input[1].Phase[x].OverCurrent[1].Threshold Parameter mA RW
PDU.Input[1].Phase[x].OverCurrent[3].Threshold Parameter mA RW
PDU.Input[1].Phase[x].OverCurrent[4].Threshold Parameter mA RW
PDU.Input[1].Phase[x].OverVoltage[1].Threshold Parameter cV RW
PDU.Input[1].Phase[x].OverVoltage[2].Threshold Parameter cV RW
PDU.Input[1].Phase[x].OverVoltage[3].Threshold Parameter cV RW
PDU.Input[1].Phase[x].OverVoltage[4].Threshold Parameter cV RW
PDU.Input[1].Phase[x].PeakFactor Measure Crest factor of the current provided by the phase. m% RO
PDU.Input[1].Phase[x].PercentLoad Measure Percent load consumed on the phase. It is the ratio: current
consumed / the nominal current of the PDU.
% RO
PDU.Input[1].Phase[x].PhaseID Constant Phase ID identifier depending of the wiring:
1: Line 1 to Neutral
2: Line 2 to Neutral
3: Line 3 to Neutral
12: Line 1 to Line 2
23: Line 2 to Line 3
31: Line 3 to Line 1
- RO
PDU.Input[1].Phase[x].PowerFactor HideMeasure Ratio of active power / apparent power provided by the
phase.
Value 0 to 100 for Cos PHI = 0.00 to 1.00
m% RO
PDU.Input[1].Phase[x].PresentStatus.OverCurrent AlarmL1 0: No threshold triggered
1: Warning low threshold triggered
2: Critical low threshold triggered
3: Warning high threshold triggered
4: Critical high threshold triggered
- RO
PDU.Input[1].Phase[x].PresentStatus.OverVoltage AlarmL1 0: No threshold triggered
1: Warning low threshold triggered
2: Critical low threshold triggered
3: Warning high threshold triggered
4: Critical high threshold triggered
- RO
PDU.Input[1].Phase[x].ReactivePower HideMeasure Reactive Power Measurement. dVA
R
RO
PDU.Input[1].Phase[x].Statistic[4].Energy HideMeasure Energy counter since last reset. As it is reset to 0, the
related timestamp is updated with the current RTC value.
Wh RO
PDU.Input[1].Phase[x].Statistic[4].ModuleReset Command - RW
PDU.Input[1].Phase[x].Statistic[4].Reset.Energy HideMeasure Energy counter saved at last reset. As it is reset, the
related timer updated with PDU timer since 1st restart.
Wh RO
PDU.Input[1].Phase[x].Statistic[4].Reset.Time HideMeasure Timestamp saved at the moment when the related energy
counter is reset.
s RO
Table 8. ePDU CLI Objects (Continued)
XML Object Name Type Description Unit Access