Serial Interface Operation
Eaton ePDU G3 Operation Manual P-164000277—Rev 1 www.eaton.com/ePDU 84
PDU.PowerSummary.iName String[31] Unit friendly name. - RW
PDU.PowerSummary.iPartNumber String[15] Part Number. - RO
PDU.PowerSummary.iProduct String[63] Product Name. - RO
PDU.PowerSummary.iReferenceNumber String[31] Technical Reference of firmware. - RO
PDU.PowerSummary.iSerialNumber String[15] Serial Number. - RO
PDU.PowerSummary.iVersion String[15] F/W Version. - RO
PDU.PowerSummary.OverTemperature[3].Threshold Parameter Threshold d°K RW
PDU.PowerSummary.OverTemperature[4].Threshold Parameter Threshold d°K RW
PDU.PowerSummary.PDUType Constant Feature Topology of the PDU:
0: Unknown
1: SW (Switched)
2: MO (Metered Outlet)
3: MA (Managed)
4: MI (Metered Input)
5: IL (In-Line Metered))
- RO
PDU.PowerSummary.PresentStatus.CommunicationLost AlarmL1 Communication intra modules have failed. - RO
PDU.PowerSummary.PresentStatus.OverTemperature AlarmL1 0 : No threshold trigged
1 : Warning low threshold trigged
2 : Critical low threshold trigged
3 : Warning high threshold trigged
4 : Critical high threshold trigged
- RO
PDU.PowerSummary.Temperature Measure Internal Temperature. d°K RO
PDU.PowerSummary.Time Measure Unix timestamp that is refreshed from the RTC. s RW
PDU.PowerSummary.Timer Measure Time elapsed since the 1st start of the device. s RO
Table 8. ePDU CLI Objects (Continued)
XML Object Name Type Description Unit Access
Table 9. System CLI Objects
XML Object Name
Access
right Type Description Access Default Value
System.Bootloader.iVersion admin String:15 RO ""
System.Bootloader.Mode superadmin BootMode 0: Normal
1: Upgrade
2: Passthru
3: ATE
4: Bootstrap
RW 0
System.Contact admin String:31 RW ""
System.DaisyChain.Count admin Integer0to65535 RO 1