What to do if Eaton UPS load is no longer supplied if AC power fails?
- KKelli MuellerSep 12, 2025
If the load is no longer supplied when AC power fails, it could be because: * The rotary switch on the HotSwap MBP module is set to the Bypass position. * The wiring between the UPS and the HotSwap MBP module is not correct. * The UPS is shutdown. Set the rotary switch on the HotSwap MBP module to the Normal position and check the wiring between the UPS and the HotSwap MBP module.