EXTERNAL BYPASS SWITCH INSTALLATION
Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide S 164201403 Rev B
www.eaton.com/powerquality
36
QFE: 50 Hz 120 Vac Input and Output OR
FE: 60 Hz 120 Vac Input and Output OR
FE 1.15–3.1 kVA only: 60 Hz 220 Vac Input and Output (with single-voltage output)
For 220 Vac, use only a BBM switch.
Figure 8. FE or QFE 500 VA–3.1 kVA UPS with External Bypass Switch
Table 11. Minimum Recommended Circuit Breakers for 60 Hz 120 Vac
Charger 500 VA, 700 VA, and 850 VA 1.15 kVA 1.4 kVA 1.8 kVA 2.1 kVA 3.1 kVA
Standard 15 15 15 20 25 35
15A 20 20 40 45 50
Table 12. Input Current for 50 Hz 120 Vac - Size Overcurrent Protection According to Local Code
Voltage and Charger 500 VA 700 VA 850 VA 1.15 kVA 1.4 kVA 1.8 kVA 2.1 kVA 3.1 kVA
120V, Standard Charger 4.4A 5.8A 7.0A 8.4A 11A 15A 16A 24A
120V, 15A Charger 8.9A 11A 12A 13A 14A 27A 28A 35A