EXTERNAL BYPASS SWITCH INSTALLATION
Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide S 164201403 Rev B
www.eaton.com/powerquality
37
Table 13. Input Current for 60 Hz 220 Vac - Size Overcurrent Protection According to Local Code
60 Hz Voltage 1.15 kVA 1.4 kVA 1.8 kVA 2.1 kVA 3.1 kVA
220V, Standard Charger 4.6A 5.8A 7.8A 9.4A 12A
220V, 15A Charger 7A 8A 15A 17A 21A
60 Hz 208 Vac or 240 Vac Input - 120/208 Vac or 120/240 Vac Output
For 208 Vac, use only a BBM switch.
Figure 9. FE 500 VA–3.1 kVA UPS with External Bypass Switch
Table 14. Minimum Recommended Circuit Breakers for 208 Vac or 240 Vac
208 Vac 240 Vac
Charger 500 VA – 1.4 kVA 1.8 kVA 2.1 kVA 3.1 kVA 500 VA – 1.4 kVA 1.8 kVA 2.1 kVA 3.1 kVA
Standard 15 15 15 20 15 15 15 15
15A 15 20 25 30 15 20 20 25