EXTERNAL BYPASS SWITCH INSTALLATION
Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide S 164201403 Rev B
www.eaton.com/powerquality
44
Table 20. Input Current - Size Overcurrent Protection According To Local Code
Voltage Charger 4.3 kVA 5.3 kVA 7 kVA 10 kVA 12.5 kVA 18 kVA
60 Hz
220 Vac
Standard 17A 21A 27A 41A 53A 81A
10A 18A 23A 28A 49A 60A 85A
20A 20A 25A 30A 52A 65A 89A
50 Hz
220 Vac
Standard 19A 21A 27A 43A 55A 81A
10A 22A 23A 28A 46A 58A 84A
20A 23A 25A 29A 51A 63A 89A
50 Hz
230 Vac
Standard 18A 20A 26A 41A 53A 78A
10A 20A 22A 27A 44A 56A 81A
20A 21A 24A 28A 49A 60A 85A
50 Hz
240 Vac
Standard 17A 19A 24A 39A 51A 75A
10A 19A 21A 26A 43A 54A 78A
20A 20A 23A 27A 47A 58A 82A