40 Eaton Ferrups FX UPS P-164000906 Eaton Ferrups FX User’s Guide P-164000906—Rev 05
Table 19. Parameter List (Continued)
Parameter
Number
Sample / Default
Password Level
Range Description
may be longer while UPS is attempting to
lock to line input again.
59
59 LVOAlrm 60.0 V No Change
Allowed
0.0 – 500.0
Setpoint at which UPS will alarm due to
lowAC volts out to the user load.
60 60 LVIAlrm 88.1 V No Change
Allowed
0.0 – 500.0
Setpoint at which UPS will alarm due to
lowAC volts into the UPS.
61 61 HVOAlrm 129.6 V
No Change
Allowed
0.0 – 500.0
Setpoint at which UPS will alarm due to
high AC volts out to the user load.
62 62 HVIAlrm 146.7 V
No Change
Allowed
0.0 – 500.0
Setpoint at which UPS will alarm due to
high AC volts into the UPS.
63 63 OvrldLv1 100 % User 10 – 100
Alarm setpoint for output overload. Alarm
condition only – no other action taken.
64 Reserved
65 65 Shtdwn 1.750 VPC User 1.670 – 2.100
When using custom batteries, the battery
voltage shutdown level, load off and UPS
shuts off. Alarm setpoint for low battery
condition.
66 66 BattLow 1.833 VPC User 1.670 – 2.100
Alarm setpoint for near low battery
condition.
Alarm condition only – no other action
taken.
67 67 OvAlarm 2.400 VPC User 2.200 – 2.600
When using custom batteries, the alarm
setpoint for high battery condition. Alarm
condition only - no other action taken.
68 68 LowRunTm 3 m User 0 – 999
Alarm setpoint for low runtime condition.
Alarm condition only – no other action
taken.
69 Reserved
70
70 LowBatCap 0 %
User 0 – 99
Low battery capacity setting, percent of
battery charge below this level causes a
low battery alarm.
71 Reserved
72 72 TestIntrl 7 d User 7 - 180
When using custom batteries, the discharge
test interval, the time between discharge
tests.
73 73 Test@ 1:00:00 User 0 - 23:59:00
When using custom batteries, the time of
day that the battery discharge test will
start.
74 Reserved
UPS Parameters