40 Eaton Ferrups FX UPS P-164000906 Eaton Ferrups FX User’s Guide P-164000906—Rev 05
Table 19. Parameter List (Continued)
Parameter
Number
Sample / Default
Password Level
Range Description
may be longer while UPS is attempting to
lock to line input again.
59
59 LVOAlrm 60.0 V No Change
Allowed
0.0 500.0
Setpoint at which UPS will alarm due to
lowAC volts out to the user load.
60 60 LVIAlrm 88.1 V No Change
Allowed
0.0 500.0
Setpoint at which UPS will alarm due to
lowAC volts into the UPS.
61 61 HVOAlrm 129.6 V
No Change
Allowed
0.0 500.0
Setpoint at which UPS will alarm due to
high AC volts out to the user load.
62 62 HVIAlrm 146.7 V
No Change
Allowed
0.0 500.0
Setpoint at which UPS will alarm due to
high AC volts into the UPS.
63 63 OvrldLv1 100 % User 10 100
Alarm setpoint for output overload. Alarm
condition only no other action taken.
64 Reserved
65 65 Shtdwn 1.750 VPC User 1.670 2.100
When using custom batteries, the battery
voltage shutdown level, load off and UPS
shuts off. Alarm setpoint for low battery
condition.
66 66 BattLow 1.833 VPC User 1.670 2.100
Alarm setpoint for near low battery
condition.
Alarm condition only no other action
taken.
67 67 OvAlarm 2.400 VPC User 2.200 2.600
When using custom batteries, the alarm
setpoint for high battery condition. Alarm
condition only - no other action taken.
68 68 LowRunTm 3 m User 0 999
Alarm setpoint for low runtime condition.
Alarm condition only no other action
taken.
69 Reserved
70
70 LowBatCap 0 %
User 0 99
Low battery capacity setting, percent of
battery charge below this level causes a
low battery alarm.
71 Reserved
72 72 TestIntrl 7 d User 7 - 180
When using custom batteries, the discharge
test interval, the time between discharge
tests.
73 73 Test@ 1:00:00 User 0 - 23:59:00
When using custom batteries, the time of
day that the battery discharge test will
start.
74 Reserved
UPS Parameters