Eaton Ferrups FX UPS P-164000906 Eaton Ferrups FX User’s Guide P-164000906—Rev 05 41
Table 19. Parameter List (Continued)
Parameter
Number
Sample / Default
Password Level
Range Description
75 75 BT Time 60 s User 60 - 180
When using custom batteries, the test will
discharge the batteries for this amount of
time.
76
76 DVR Temp 28 C
No Change
Allowed
–63 – 193
Temperature in degrees C of the highest
reading of the two temperatures sensors on
DVR.
77
77 BatAlmDly 5 s
User 0 - 300
Number of seconds to delay before setting
the On Battery alarm after the UPS goes on
battery.
78
78 AlmEnbl 1)Yes
No Change
Allowed
0)No
Permanently enables and disables the alarm
beeper. Changes by initiating a Control 5
Enter, Enter Command via the RCD.
1)Yes
79
79 IntrnlBuzzr 0)Off
User
0)Off
Switch On/Off buzzer from control board.
1)On
80 80 AT Alarm 60 C Service 0 – 200
Ambient temperature setpoint at which UPS
will alarm. Programming to 0 will disable
Probe Missing alarm.
81
81 AutoMaxPLLError
10.0
User 0.0 – 6553.5
Maximum Angle Error allowed by the PLL to
remain locked in Auto Mode.
82
82 LCMaxPLL Error
30.0
User 0.0 – 6553.5
Maximum Angle Error allowed by the PLL to
remain locked in Line Condition Mode.
83
83 UtilityPLLSense
2
User 1 – 50
Sets how many readings beyond the
maximum angle error are required for the
PLL to lose lock.
84
84
AutoTapSwDebounce
0.025
User 0.0 – 12.844
Sets the debounce period for determining
when to tap switch in Auto Mode.
85
85 LCTapSwDebounce
0.030
User 0.0 – 12.844
Sets the debounce period for determining
when to tap switch in Line Condition Mode.
86–89 Reserved
90
90 Custom Batt 0)No
User
0)No
Selects using custom batteries. Disables
ABM. Battery runtime will not be accurate.
1)Yes
91
91 BatAmpHrs 0AH
User 0 – 2000
When using custom batteries, the Amp-hour
capacity of batteries in UPS.
92
92 ABM 1)Enabled
User
0)Disabled
ABM enable.
1)Enabled
93 93 AbmIntrvl 3 mo User
3,4,5,6 Months
ABM Discharge Test Interval.
94
94 Chrgr 1)Enabled
User
0)Disabled
Charger enable.
1)Enabled
UPS Parameters