Eaton Ferrups FX UPS P-164000906 Eaton Ferrups FX User’s Guide P-164000906—Rev 05 43
Table 19. Parameter List (Continued)
Parameter
Number
Sample / Default
Password Level
Range Description
112
112 Minislot 1 Baud
2400
No Change
Allowed
Baud rate of communication on Minislot 1.
The interface defaults to 2400 until
negotiated higher.
113
113 Minislot 1 IPv4
0.0.0.0
No Change
Allowed
IPv4 Address of network card on Minislot 1.
114
114 Minislot 2 Baud
2400
No Change
Allowed
Baud rate of communication on Minislot 2.
The interface defaults to 2400 until
negotiated higher.
115
115 Minislot 2 IPv4
0.0.0.0
No Change
Allowed
IPv4 Address of network card on Minislot 2.
116
116 Minislot 1 Reset
0)Inactive
User
0)Deactivate Reports present condition of Minislot 1
reset line. Allows resetting the
communication port for Minislot 1.
1)Activate
117
117 Minislot 2 Reset
0)Inactive
User
0)Deactivate
Reports present condition of Minislot 2
reset line. Allows resetting the
communication port for Minislot 2.
1)Activate
118
118 SiteWiringDetect
1)Enabled
User
0)Disabled
Allows enabling and disabling of checking
for site wiring fault.
1)Enabled
119
119 AutoRestart 1)
Enabled
User
0)Disabled
Allows enabling and disabling of Auto
Restart feature.
1)Enabled
120
120 ROO Active 1)
High
User
0)Low
Sets the active level for the Communication
Remote On/Off input.
1)High
121
121 OnGen Active 1)
High
User
0)Low
Sets the active level for the On Generator
input.
1)High
122
122 Bypss Active 0)
Low
User
0)Low
Sets the active level for the Maintenance
Bypass input.
1)High
123–128 Reserved
129
“129 LoACDly 40 s” Factory
1 255
Alarm debounce time in seconds until low
AC out alarm/shutdown occurs.
130 “130 BOostV 86.25 %”
No Change
Allowed
60.00 276.00
If the AC input voltage is below this level
and above the brownout voltage, the UPS
will switch to the boost tap. (NOTE:
parameter 133 is applied to this set point to
provide hysteresis)
131
“131 BucKV 105.58
%”
No Change
Allowed
60.00 276.00
If the AC input voltage is above this level
the UPS will switch to the buck tap. (NOTE:
parameter 133 is applied to this set point to
provide hysteresis)
132 Reserved