66 Eaton Ferrups FX UPS P-164000906 Eaton Ferrups FX User’s Guide P-164000906—Rev 05
Table 29. Typical Alarm Conditions (Continued)
13
CONTROL POWER
ON
Status UPS is ok Turning On Nothing.
14
HARDWARE
INCOMPATIBILI-
TY
A Hardware doesn’t match
unit rating
Off Nothing.
15
PWR BRD EE
FAILURE
A
Corrupt hardware Off Turn UPS off. Call Eaton
Service.
16
BATTERY NEEDS
SERVICE
A Batteries need
replacement.
Normal operation but
Charger off.
Turn UPS off. Replace
Batteries – call Eaton
Service.
17
CTO CONFIG
ERROR
A Hardware check needed Off Call Eaton Service
18
OS FAILURE A UPS Failure Off Power Cycle and recheck.
Call Eaton Service if
problem persists.
19
LEVEL 1
OVERLOAD
N Load > 100% but <
105%
Normal mode supporting
load
Reduce Load to < 100% (5%
hysteresis for alarm to clear)
20 LEVEL 2
OVERLOAD
A Load > 105% but <
115%
Supporting Load but only for
a short time (minimum 10
minutes)
Reduce Load to < 100% (5%
hysteresis for alarm to clear)
21 LEVEL 3
OVERLOAD
A Load > 115% Will shut off in a short time
(minimum 10 seconds)
Reduce Load to < 100% (5%
hysteresis for alarm to clear)
22
SYSTEM
INITIALIZATION
ERROR
A Control Board failure Off Power Cycle and recheck.
Call Eaton Service if
problem persists.
23
FPGA FAILURE A Control Board failure Off Call Eaton Service
24
USB PORT
CHANGE
N Front or back USB Port
usage toggled.
Normal operation Nothing.
25
UPS ON
COMMAND
Command Turn UPS ON Turns ON
Nothing.
26
UPS OFF
COMMAND
Command Turn UPS OFF Turns OFF Nothing.
27
CHARGER OFF
COMMAND
Command Turn Charger off Normal with charger off Not Recommended. Only do
this if you are going to use
an external charger.
28
CHARGER ON
COMMAND
Command Turn Charger ON Normal with charger on Nothing
29
LOW BATTERY
SHUTDOWN
A Unit shutdown after
reaching a low battery
condition.
Off or in Keep-Alive- Mode Check input circuit breaker
and turn it on if AC Input is
OK.
31
REMOTE
EMERGENCY
POWER OFF
A Off Check why REPO was
activated at your site Check
REPO Wiring at signal input
on back of UPS.
Alarm Conditions