119FX6000 INSTALLATION AND OPERATION MANUAL 25-14683-C December 2019 www.eaton.com
Appendix
Zone monitor unit wiring (CZMU352)
Installation
1. Separate the two halves of the unit
2. Drill out (or knock out) the required cable entries in the surface
mounting back - box
3. Fit the back-box in position and pass the wires into it
4. Connect the unit according to the diagram below
ote: N No addressing of the interface is required. See control panel
operation for details
Standard Connections
ote: N
1. This unit can only be used with CDB300/I detector base and compatible detectors
2. Only connect cable screen to its adjacent earth terminal
3. The end of line resistor must always be fitted, even if the spur is unused
4. Maximum spur length - See BS5839 Pt1:2002 for Zone Coverage
5. Maximum number of call points allowed is unlimited
6. Detector zone end of line device is EOLM-1 (supplied)
7. Callpoint zone has end of line resistor
EE
LLOO OO PP
OO UU TT
IINN
CC AALL LL
PP OO IINNTT
ZZ OO NNEE
DDEE TT EE CC TTOO RR ZZOO NNEE
EE
EE EE
--
--
-- --
++
++
++ ++
- OUT +
- IN +
- OUT +
- IN +
12K
Analogue Addressable Loop
Callpoints can be connected with detectors
on detector zone if preferred