31FX6000 INSTALLATION AND OPERATION MANUAL 25-14683-C December 2019 www.eaton.com
Equipment compatibility
Equipment compatibility
Sensors
Loop wired sensors must be of the Eaton Fire Systems soft addressed analogue
type. Eaton Fire Systems conventional detectors can be connected via an CZMU352
interface. The connection of other detector types via an CZMU352
interface is not recommended.
Call points
Loop wired call points must be the Eaton Fire Systems soft addressed analogue
type, Eaton Fire Systems conventional callpoints can be connected via an CZMU352
interface. The connection of other callpoint types via an CZMU352 interface
is not recommended,
Sounders
Loop powered addressable sounders must be of the Eaton Fire Systems soft
addressed analogue type.
Conventional sounders can also be connected either to the conventional sounder
circuits at the panel or to the loop via a CSC354 addressable sounder controller
interface providing they meet the following:
•
They are suitable for operation between 18V and 28V
•
They are polarised and suppressed
•
The total alarm load is less than the rating of the panel/Alarm Power Interface
ote: N It is possible to use devices outside these requirements if they are supplied
with power from a separate source and switched via a suitable relay.
Relay circuits
Additional relays can be added to the system by using either
CMIO353 or CIO351 relay units.