54 FX6000 INSTALLATION AND OPERATION MANUAL 25-14683-C December 2019 www.eaton.com
Maintenance
Maintenance
Functions: See User Manual for full details.
Daily inspection
Check that only the green “POWER ON” indicator shows. Inspect for any fault
indication. Notify any faults to a system supervisior.
Weekly test
Check indicators.
Press Supervisor mode on the top left of the touch screen. Enter passcode.
Select others” tab. Press the button labled weekly test, confirm you wish to
perform the test and the amber “System Test” LED will light. The panel will stay
in weekly test mode until the system is manually reset. During the weekly test,
trigger a smoke Sensoror call point and check the fire panel registers the device and
illuminates the correct zonal indicator. Trigger a different device every time a weekly
test is performed ensuring devices are tested in rotation until all have been checked.
It is advisable to develop a detailed building plan highlighting devices and locations to
aid testing. Record weekly test in the table provided in this log book.
Quarterly
Check all previous log book entries and verify that remedial action has been taken.
Carry out the weekly test. Visually examine the batteries and their connections, by
loosening the screws behind printer door and opening the hinged front from the right
hand side.
Disconnect the mains supply and check that the battery is capable of supplying the
alarm sounders, by operating a call point.
Annual test
As Weekly Test and Quarterly Test above. Additionally test all sensors and call points
and check operation.
Every 2-3 years
During the normal servicing cycle check analogue levels of the detectors. If any
are approaching the pre-alarm level then the proprietary cleaning methods can be
adopted. e.g. high pressure air spray.
Every 5 years
Replace sealed lead acid battery.