Installation i-on30EX/EXD
Page 20
connections are different on the expander
compared to the control unit.
Figure 31 shows wiring for four-wire CCL zones
on the KEY-KPZ01.
Figure
Control Unit CCL Zone Wiring
Figure 29 shows the wiring for four-wire CCL
zones on the wired expander. Note that the
connections are different on the expander
compared to the control unit. Also note that zones
0, 6,7,8 and 9 are not available on the control unit,
and zones 5-9 are not available on the expander.
Figure
Wired Expander CCL Zone Wiring
Figure 30 shows the wiring for CCL zones on the
EXP-WCC wired expander. Note that the EXP-
WCC provides connectors for a total of ten
separate 4-wire CCL detectors, and that there are
separate terminals for both alarm and tamper.
Figure
KEY-KPZ01 CCL Zone Wiring
Two-Wire Closed Circuit Connections
With version 4.02 and higher software you can
connect two-wire CCL detectors to each pair of
zone terminals. To specify the zone wiring type
use the Installer Menu – System Options – Wire Zone
Type option and select “2-wire CC”.
On the control unit, EXP-W10 and EXP-WCC, if
required you can use one pair of zone terminals
as a common tamper, provided you program that
zone with the type “Tamper” from the Installer
Menu.
The EXP-WCC does not specifically have a 2-wire
CC zone type. However you can mimic the setting
by using “4k7/2k2/4-wire CC” zone wiring option,
and then connecting the detector to the alarm
terminals and placing a short across the tamper
terminals.
Fully Supervised Loop Connections
Figure 32 shows the wiring connections for FSL
zones on the control unit. Note that the resistance
values shown are examples.