MVX9000 Parameter Listing
B-8 MVX9000 User Manual
Parameter Tables
Table B-4: 50 — DRIVE CONTROL (Continued)
Modbus Groups Page # Description Range Default
User
Settings
0322H 50.35 5-41 Feedback Signal
Selection
00: Positive AI1 (0 – 10V)
01: Negative AI1 (0 – 10V)
02: Positive AI2 (4 – 20 mA)
03: Negative AI2 (4 – 20 mA)
00
0323H 50.36 5-41 P Gain Adjustment 0.0 to 10.0 1.0
0324H 50.37 5-41 I Gain Adjustment 0.00 to 100.0 sec 1.00
0325H 50.38 5-41 D Gain Adjustment 0.00 to 1.0 sec 0.00
0326H 50.39 5-42 Upper Limit of
Integral Control
00 to 100% 100
0327H 50.40 5-42 PID Output Delay
Filter Time
0.0 to 2.5 sec 0.0
0328H 50.41 5-42 4 – 20 mA Input Loss
Detection Time
00: Disable
0.1 to 3600 sec
60
0329H 50.42 5-42 4 – 20 mA Input Loss
Operation
00: Warn and Inverter Stop 00
01: Warn and Continue
Operation
032AH 50.43 5-42 PID Set Point 0.0 to 400.0 Hz (100.0%) 0.0
032BH 50.44 5-43 PLC Operation Mode 00: Disable PLC performing 00
01: Execute one program
cycle
02: Continuously execute
program cycles
03: Execute one program
cycle step by step
04: Continuously execute
program cycles step by step
032CH 50.45 5-45 PLC Forward/Reserve
Motion
00 to 127 00
032DH 50.46 5-46 Time Duration of 1st
Preset Speed
0 to 9999 0
032EH 50.47 5-46 Time Duration of 2nd
Preset Speed
0 to 9999 0
032FH 50.48 5-46 Time Duration of 3rd
Preset Speed
0 to 9999 0
0330H 50.49 5-46 Time Duration of 4th
Preset Speed
0 to 9999 0
0331H 50.50 5-46 Time Duration of 5th
Preset Speed
0 to 9999 0
0332H 50.51 5-46 Time Duration of 6th
Preset Speed
0 to 9999 0
0333H 50.52 5-46 Time Duration of 7th
Preset Speed
0 to 9999 0